The LIOB-45x Modules are LonMark certified and communicate over Ethernet/IP-852 in the LonMark System. They provide up to 512 address table entries (ECS mode) which eliminates all binding restrictions.

LonMark IP-852 Channel over Ethernet

The LIOB-45x I/O Modules are equipped with two Ethernet ports including a built-in Ethernet switch. This allows for building a daisy chained line topology of up to 20 devices, which reduces costs for network installation. Dual Ethernet port devices also allow the setup of a redundant Ethernet installation (ring topology), which increases reliability. The redundant Ethernet topology is enabled by the Rapid Spanning Tree Protocol (RSTP), which is supported by most managed switches.

The LIOB-45x Modules are equipped with a Web interface to query the device status. The local display can be accessed via VNC.

LIOB-IP Mode

The LIOB‑45x Modules can be switched to LIOB‑IP mode using manual local operation. In LIOB‑IP mode, the LIOB‑45x Modules extend L‑INX Automation Servers, L‑ROC Room Controllers, L-IOB I/ O Controllers and LIOB-AIR I/ O Controllers with physical inputs and outputs via plug and play.

Local Operation and Override

All L-IOB I/O Modules are equipped with an LCD display (128x64) with backlight and jog dial for manual local operation. Device and data point information is displayed in text form and via graphical symbols.

 

L-INX I/O Integration through LIOB-IP via Plug 'n Play

 

Plug and play I/O integration through LIOB-IP

LIOB-IP852 I/O Modules LonMark Products


LIOB-450
LIOB-450

LIOB-IP852 I/O Module: 8 UI, 2 DI, 2 AO, 8 DO (4 x Relay 6 A, 4 x Triac 0.5 A)

Add this product to the Request for Quote
Related documents and software for LIOB-450
3D View for LIOB-450

LIOB-451
LIOB-451

LIOB-IP852 I/O Module: 8 UI, 12 DI

Add this product to the Request for Quote
Related documents and software for LIOB-451
3D View for LIOB-451

LIOB-452
LIOB-452

LIOB-IP852 I/O Module: 6 UI, 6 AO, 8 DO (8 x Relay 6 A)

Add this product to the Request for Quote
Related documents and software for LIOB-452
3D View for LIOB-452

LIOB-453
LIOB-453

LIOB-IP852 I/O Module: 6 UI, 6 AO, 5 DO (4 x Relay 16 A, 1 x Relay 6 A)

Add this product to the Request for Quote
Related documents and software for LIOB-453
3D View for LIOB-453

LIOB-454
LIOB-454

LIOB-IP852 I/O Module: 7 UI, 4 AO, 7 DO (5 x Relay 6 A, 2 x Triac 0.5 A), 1 Pressure Sensor

Add this product to the Request for Quote
Related documents and software for LIOB-454
3D View for LIOB-454

LPOW-2415A
LPOW-2415A

LIOB-Connect Power Supply, 24 VDC, 15 W

Add this product to the Request for Quote
Related documents and software for LPOW-2415A
3D View for LPOW-2415A

LPOW-2415B
LPOW-2415B

Power supply unit with power connector 24 VDC, 15 W

Add this product to the Request for Quote
Related documents and software for LPOW-2415B
3D View for LPOW-2415B

L-TEMP2
L-TEMP2

External temperature sensor (NTC10K) for use with L-IOB Universal Inputs

Add this product to the Request for Quote
Related documents and software for L-TEMP2


Features

  • I/O module with physical inputs and outputs
  • Ethernet/IP network interface
  • SNVT-based interface for integration on the LonMark IP-852 channel
  • LonMark certified
  • Up to 512 address table entries (ECS mode)
  • Manual operation using the jog dial
  • 128x64 graphic display with backlight
  • Local access to information about device status and data points in clear text and symbols
  • Connected to the L‑INX Automation Server, L‑ROC Room Controller, L-IOB I/O Controller, and LIOB-AIR I/O Controller via LIOB‑IP
  • Automatic integration into device configurations with L‑INX, L‑ROC, L-IOB I/O Controller, and LIOB-AIR
  • Easy device replacement without any additional software
  • Integrated Web server for the device configuration
  • LNS plug‑in for the device configuration in the LonMark System

Specification

Dimensions in mm [inch]

LIOB-450

LIOB-450_dimensions

LIOB-451

LIOB-451_dimensions

LIOB-452

LIOB-452_dimensions

LIOB-453

LIOB-453_dimensions

LIOB-454

LIOB-454_dimensions
 
 
General Specifications
Dimensions (mm) 107 x 100 x 75 (L x W x H)
Operating conditions 0 °C to 50 °C, 10 – 90 % RH, non condensing, degree of protection: IP40, IP20 (terminals)
Power supply 24 V DC / 24 V AC ±10 % via L‑INX, L‑ROC, L‑POW or LIOB‑A2/A4 via LIOB‑Connect
Interfaces
2 x Ethernet (100Base-T)
LIOB-IP
LonMark IP-852
Specifications LIOB‑IP852 I/O Module (LIOB‑45x)
Types LIOB‑450 LIOB‑451 LIOB‑452 LIOB‑453 LIOB-454
Power consumption
4.5 W (all Relays on)
4.5 W
4.5 W (all Relays on)
4.5 W (all Relays on)
4.5 W (all Relays on
Universal Input (UI) 8 8 6 6 7
Digital Input (DI) 2 12 - -  
Analog Output (AO) 2 - 6 6 4
Digital Output (DO) 8 (4 x Relay 6 A, 4 x Triac 0.5 A) - 8 (8 x Relay 6 A)

5 (4 x Relay 16 A,
1 x Relay 6 A)

7 (5 x Relay 6 A, 2 x Triac 0.5 A)
Digital Output specification Please refer to the “General Input and Output Specification of LOYTEC devices” for more details.

Differential Pressure Sensor  -  -  -  - 0–500 Pa

Resource limits
Network variables (NVs) Fixed static NV interface
Address table entries 512 (non-ECS mode: 15)

General Input and Output Specification of LOYTEC devices

UI Universal Input

UIs are universal inputs for four different input types. They have an input voltage range of 0 V to 10 V, and can withstand up to 30 V. The UIs correspond to class 1 with a relative accuracy of ±1 % (of measured value) between 1 V and 10 V, and an absolute accuracy of ±10 mV between 0 V and 1 V. The ADC resolution is 16 bits. Galvanically isolated sensors resp. switches must be connected. Universal inputs can be configured as:

  • Binary Input (Digital Input)

    Input impedance > 20 kΩ, sampling period 10 ms.
    • In voltage mode, the threshold values are < 0.8 V for low level and > 2 V for high level.
    • In resistance mode, the threshold values are < 1.9 kΩ for low level and > 6.7 kΩ for high level.
    Between the threshold values, the resulting level of the UI is not defined.
  • Voltage Metering 0-10 V

    Input Impedance > 20 kΩ, sampling period < 1 s.
  • Current loop 4-20 mA

    Input Impedance > 20 kΩ, sampling period < 1 s. An internal shunt of 249 Ω is available for some universal inputs. Otherwise, an external resistor of 249 Ω must be used as a shunt.
  • Resistance Measurement

    Input Impedance 10 kΩ, sampling period < 1 s. Resistors in the range of 1 kΩ to 100 kΩ can be measured. For popular temperature sensors (e.g. Pt1000, NTC10K, NTC1K8, Ni1000) fixed internal translation tables are provided. For all other temperature sensors, translation tables can be defined in the configuration tool and used on the device.

The average sampling period p of analog inputs depends on the number of active (non-disabled) universal inputs n that are configured in analog mode. The formula for p is:

p = n * 125 ms

This means if e.g. only two UIs are configured as analog inputs, a new sample is taken every 250 ms (on average) for each of the two inputs. The UIs configured as digital inputs are unaffected (sampling period always 10 ms) by this formula.

DI – Digital Input, Counter Input (S0-Pulse)

DIs are fast binary inputs, which can also be used as counter inputs (S0). They follow the S0 specification for electric meters and have a sampling rate of 10 ms. They change state at a load of 195 Ω between the DI terminal and GND. Galvanically isolated sensors resp. switches must be connected.

AO – Analog Output

AOs are analog outputs with a signal range of 0 to 10 V (up to 12 V), a resolution of 10 bits, and a maximum output current of 10 mA (20 mA @ 12 V), short circuit proof (2 outputs at a time). The accuracy over the whole range is ±100 mV.

DO – Digital Output

The following digital outputs are available:

  • Relay 6A Output: Switching capacity 6A, 250VAC resp. 30VDC. Max in-rush current 6A, max. 600W (resistive) @ 250VAC.
  • Relay 10A Output: Switching capacity 10A, 250VAC resp. 30VDC. Max in-rush current 10A, max. 1600W (resistive) @ 250VAC.
  • Relay 16A Output: Switching capacity 16A, 250VAC resp. 30VDC. Max in-rush current 80A, max. 2000W (resistive) @ 250VAC.
  • TRIAC Output: Switching capacity 0.5A, 24 to 230VAC. External relays must not be connected.

When switching higher loads than specified an interface relay must be used and a quenching circuit like a varistor or RC element must be used at the selected LOYTEC device.

PRESS – Pressure Sensor

These inputs represent differential pressure sensors. They are equipped with two 3/16” (4.8 mm) hose connectors.