EU Cookie Law Script 1

     We use cookies to make our websites easier to use. By browsing our websites you agree to our use of cookies.

L-STAT - Video

L-STAT Network Thermostat

L STATs

Index

Specifications

Dimensions in mm [inch]

LSTAT-800-Gx, LSTAT-801-Gx, LSTAT-802-Gx

L-STAT_dimensions

Specifications
Type LSTAT-800-Gx-Lxxx LSTAT-801-Gx-Lxxx LSTAT-802-Gx-Lxxx
Dimensions (mm) 94.5 x 110 x 19.5 (W x H x D)
Installation

Onto a flush-mounted box

Power Supply

24 V DC ±10 %, max. 0.8 W

24 V DC ±10 %, max. 1.8 W
Operating conditions 0 °C to 50 °C, 10 – 90 % RH, non condensing, degree of protection: IP30
Display LCD display with backlight, and choice of RGB color
Interfaces, sensors

1 x RS‑485 (ANSI TIA/EIA-485): Modbus RTU (Slave), adjustable bus speed 1 200 – 115 200 bit/s (typical 57 600 bit/s),
configurable transmission mode (typical “8E1”, 1 start bit, 8 data bits, even parity, 1 stop bit)

1 x NFC (Near Field Communication)
1 x Buzzer
1 x Internal temperature sensor
1 x Internal relative humidity sensor
3 x Digital Input for connection of standard switches and pushbuttons
1 x Universal Input, configurable either for L-TEMP2 (NTC temperature sensor) or for connection of standard switches and pushbuttons
1 x Infrared receiver
-
1 x Occupancy sensor
- -
1 x CO2 sensor
Buttons (capacitive touch)

LSTAT-80x-Gx-Lxx1: 4 x Button with temperature up/down, occupancy, and menu

LSTAT-80x-Gx-Lxx2: 6 x Button with temperature up/down, fan up/down, occupancy, and menu

LSTAT-80x-Gx-Lxx3: 8 x Button with temperature up/down, fan up/down, light on/off, occupancy, and menu

LSTAT-80x-Gx-Lxx4: 8 x Button with temperature up/down, sunblinds up/down, light on/off, occupancy, and menu

LSTAT-80x-Gx-Lxx5: 8 x Button with temperature up/down, fan up/down, sunblinds up/down, occupancy, and menu

LSTAT-80x-Gx-Lxx6: 8 x Button with temperature up/ down, fan up/down, sunblinds up/down, light, and menu

For use with L-INX, LIOB‑AIR and L-ROC Controller, Modbus Master via Modbus RTU

 

Specifications of the sensors
Temperature measurement Sensor type: CMOS, range: -40 – 125 °C, resolution: 0.1 °C, accuracy: ±0.5 °C (5 – 60 °C)
Relative Humidity (R.H.)
Sensor type: capacitive humidity sensor, range: 0 % – 100 % R.H., resolution: 0.1 % R.H.,
accuracy:
±2 % R.H. @ 25 °C, 20 % – 80 % R.H.
±3 % R.H. @ 25 °C, 0 % – 20 % R.H. and 80 % – 100 % R.H., respectively
Infrared occupancy detector, maximum detection range 5 m, 64 zones, opening angle horizontal: 94°, vertical: 82°, difference in temperature: target to environment: > 4 °C
CO2 0 – 2 000 ppm, ±30 ppm or ±3 %
Infrared receiver NEC protocol (Apple remote compatible)