EU Cookie Law Script 1

     We use cookies to make our websites easier to use. By browsing our websites you agree to our use of cookies.

Video: Features der L-INX 6.4 Release

LINX-215 Automation Server

LINX 215

Index

Specification

Dimensions in mm [inch]

LINX-215

LINX-215_dimensions

Specifications
Dimensions (mm) 107 x 100 x 75 (L x W x H)
Installation DIN rail mounting following DIN 43880, top hat rail EN 50022
Power supply 24 V DC / 24 V AC ±10 %, typ. 2.5 W
Operating conditions 0 °C to 50 °C, 10 – 90 % RH, non condensing, degree of protection: IP40, IP20 (terminals)
Interfaces 2 x Ethernet (100Base-T):
OPC XML‑DA, OPC UA,
LonMark IP‑852, BACnet/‌IP,
LIOB‑IP,
KNXnet/‌IP,
Modbus TCP (Master or Slave),
HTTP, FTP, SSH, HTTPS, Firewall, VNC, SNMP
1 x LIOB‑Connect
1 x RS‑485 (ANSI TIA/‌EIA‑485):
BACnet MS/‌TP
or
Modbus RTU (Master or Slave)

1 x FT
1 x EXT:
M‑Bus, Master EN 13757‑3
(needs L‑MBUS20 or L‑MBUS80)
or
KNX TP1 (needs LKNX‑300)
or
SMI (needs LSMI-800)
2 x USB-A:
WLAN (needs LWLAN‑800), EnOcean (needs LENO‑80x), SMI (needs LSMI-804), LTE (needs LTE-800), MP-BUS (needs LMPBUS-804)

L‑IOB I/O Modules Up to 8 L‑IOB I/‌O Modules in any combination of type LIOB‑10x, LIOB‑15x, LIOB‑45x and LIOB‑55x
Remote Network Interface 1 RNI with 2 MNI devices
CEA‑709 Router 1
Program cycle time Down to 10 ms
Runtime licences
Type LINX-215
Programming, Tools L‑STUDIO (IEC 61131‑3 and IEC 61499 based), L‑INX Configurator
Licence

L‑STUDIO: included
L‑LOGICAD: included

 

Resource limits
Total number of data points 10 000 Address table entries 1 000 („non-ECS mode“: 15)
OPC data points 2 000 LonMark Calendar 1 (25 calendar patterns)
BACnet objects 750 (analog, binary, multi-state) LonMark Scheduler 100
BACnet client mappings 750 LonMark Alarm Server 1
BACnet calendar objects  25 Total trended data points 256
BACnet scheduler objects 100 (64 data points per object) E-mail templates 100
BACnet notification classes 32 Math objects 100
Trend logs (BACnet or generic) 256 (4 000 000 entries, ≈ 60 MB) Alarm logs 10
Network variables (NVs) 1 000 M-Bus data points 1 000
Alias NVs 1 000 Modbus data points 2 000
External NVs (polling) 1 000 MP-Bus devices (per channel) 16
KNXnet/IP data points 250 KNX TP1 data points 250
Connections (Local / Global) 1 000 / 250 L-IOB I/O Modules 8
Number of L-WEB clients 32 (simultaneously) Number of EnOcean devices 25
SMI devices (per channel) 16 EnOcean data points) 250