EU Cookie Law Script 1

     We use cookies to make our websites easier to use. By browsing our websites you agree to our use of cookies.

Room Automation - Video

LROC-102 Room Controller

LROC-102

Index

Specification

Dimensions in mm [inch]

LROC-102

 LROC-102 Dimensions

 

General Specifications
Dimensions (mm) 159 x 100 x 75 (L x W x H)
Installation DIN rail mounting following DIN 43880, top hat rail EN 50022 
Power supply 24 V DC / 24 V AC ±10 %, typ. 2.5 W
Operating conditions 0 °C to 50 °C, 10 – 90 % RH, non condensing, degree of protection: IP40, IP20 (terminals)
Specifications
Type
LROC-102
Interfaces  2 x Ethernet (100Base-T):
Web services (OPC XML‑DA, OPC UA), LonMark IP‑852*, BACnet/ IP**, LIOB‑IP, KNXnet/ IP,
Modbus TCP (Master or Slave), HTTP, FTP, SSH, HTTPS, Firewall, SNMP
1 x LIOB‑Connect
2 x USB-A: WLAN (needs LWLAN‑800), EnOcean (needs LENO‑80x),
MP-Bus (needs LMPBUS-804), SMI (needs LSMI-804), LTE (needs LTE-800)
1 x TP/ FT‑10* (LonMark System)
1 x LIOB‑FT
2 x RS‑485 (ANSI TIA/ EIA‑485):
BACnet MS/ TP** or
Modbus RTU (Master or Slave)
2 x EXT:
M‑Bus, Master EN 13757‑3
(needs L‑MBUS20 or L‑MBUS80)
or KNX TP1 (needs LKNX‑300)
or SMI (needs LSMI-800)
  * Router between LonMark IP‑852 and TP/ FT‑10
** Router between BACnet/ IP and BACnet MS/ TP
L‑IOB I/O Modules Up to 24 L‑IOB I/ O Modules in any combination of type LIOB‑10x, LIOB‑15x, and LIOB‑45x/55x
BACnet/‌IP Router 1
LonMark CEA-709 Router
1
Program cycle time Event-triggered
Programming, tools L‑STUDIO (IEC 61499 based)
Resource limits
Total number of data points
30 000
LonMark Schedulers 100
OPC data points 10 000 LonMark Alarm Servers 1
BACnet objects 2 000(analog, binary, multi-state) E-mail templates 100
BACnet client mappings 5 000 Math objects 100
BACnet calendar objects 25 Alarm logs 10
BACnet scheduler objects 100 (64 data points per object) M-Bus data points 1 000
BACnet notification classes 32 Modbus data points 2 000
Trend logs (BACnet or generic)
512 (4 000 000 entries, ≈ 60 MB)
KNX TP1 data points 1 000
Total trended data points 1 000 KNXnet/IP data points 1 000
CEA-709 network variables (NVs) 2 000 Connections (Local / Global) 2 000 / 250
CEA-709 Alias NVs 2 000 Number of L-WEB clients 32 (simultaneously)
CEA-709 External NVs (polling) 1 000 L-IOB I/O Modules 24
CEA-709 address table entries 1 000 (non-ECS mode: 15) Number of EnOcean devices 100
LonMark Calendar 1 (25 calendar patterns) EnOcean data points 1 000
SMI devices (per channel) 16 MP-Bus devices (per channel)  8 (16 MPL)