General Specifications
Dimensions (mm) 340 x 144 x 70 (L x W x H)
Installation mountable directly via two oblong holes (ø 7 mm, distance 315 mm) or system distribution box LBOX-ROC1, (L x W x H in mm)
Power supply 24 V DC or 85 – 240 V AC, 50 – 60 Hz (do not connect 24 V DC if SMI or DALI are used) 
Operating conditions 0 °C to 40 °C, 10 – 90 % RH, non condensing, degree of protection: IP40, IP20 (terminals)
Specifications
Type
LROC-400
LROC-401
LROC-402
Power consumption
max. 15 W 
max. 15 W
max. 15 W 
Interfaces

2 x Ethernet (100Base-T):
Web services (OPC XML‑DA, OPC UA), LonMark IP‑852, BACnet/‌IP*, LIOB‑IP, KNXnet/‌IP, Modbus TCP (Master or Slave), HTTP, FTP, SSH, HTTPS, Firewall, VNC, SNMP
1 x L-STAT (Room Operator Panel)
1 x MP-Bus (actuator)
1 x KNX TP1

2 x USB-A:
WLAN (needs LWLAN‑800),
MP-Bus (benötigt LMPBUS-804),
SMI (needs LSMI-804),
LTE (needs LTE-800)

1 x RS‑485 (ANSI TIA/‌EIA‑485):
BACnet MS/‌TP*
or
Modbus RTU (Master or Slave)
1 x DALI with integrated DALI bus power supply 16 V DC, 160 mA guaranteed supply current, 250 mA max. supply current
1 x SMI (Standard Motor Interface Master)
1 x EnOcean (Europe 868 MHz) with external antenna
1 x EXT:
M‑Bus, Master EN 13757‑3
(needs LMBUS-20 or LMBUS‑80)
or
SMI (needs LSMI-800)

2 x USB-A:
WLAN (needs LWLAN‑800),
MP-Bus (benötigt LMPBUS-804),
SMI (needs LSMI-804),
LTE (needs LTE-800)

1 x RS‑485 (ANSI TIA/‌EIA‑485):
BACnet MS/‌TP*
or
Modbus RTU (Master or Slave)
1 x DALI with integrated DALI bus power supply 16 V DC, 160 mA guaranteed supply current, 250 mA max. supply current
1 x SMI (Standard Motor Interface Master)
1 x EnOcean (Europe 868 MHz) with external antenna
1 x EXT:
M‑Bus, Master EN 13757‑3
(needs LMBUS-20 or LMBUS‑80)
or
SMI (needs LSMI-800)

2 x USB-A:
WLAN (needs LWLAN‑800),
MP-Bus (benötigt LMPBUS-804),
EnOcean (needs LENO‑80x),
SMI (needs LSMI-804),
LTE (needs LTE-800)

-

* Router between BACnet/‌IP and BACnet MS/‌TP

Universal Input (UI)
10
 
0
10
Digital Input (DI)
2
 
0
2

Analog Output (AO)

8  0 8
Digital Output (DO) 32 (24 x Relay 10 A, 8 x Triac 0.5 A)  0 32 (24 x Relay 10 A, 8 x Triac 0.5 A)
Digital Output specification
Please refer to the “General Input and Output Specification of LOYTEC devices” for more details.
Frequency 868.3 MHz  868.3 MHz -
RF Output Power 3 dBm  3 dBm -
L‑IOB I/O extension

2 L‑IOB I/‌O Modules of Type LIOB‑45x or LIOB‑55x

BACnet/‌IP Router 1
Program cycle time Event-triggered
Programming, tools L‑STUDIO (IEC 61499 based)
Max. number of Rooms/‌Segments 8  16 8
SMI devices (via built-in interface)

1 x 16

1 x 16 -
SMI devices via LSMI-800 1 x 16 1 x 16 1 x 16
SMI devices via LSMI-804 4 x 16 4 x 16 4 x 16
SMI devices (maximum) 96 96 64
EnOcean devices (via built-in interface) 32 64 -
EnOcean devices via LENO‑80x - - 32
EnOcean devices (maximum) 64 64 64
EnOcean devices commissioning limit 32 64 32
L-STAT Network Thermostats 8  6 8
DALI devices 64  64 0
DALI groups 16  16 -
DALI sensors 16  16 -
DALI pushbuttons (LDALI‑BM2) 64 pushbutton coupler  64pushbutton coupler -
MP-Bus devices (via built-in interface) 1 x 8 (16 MPL) 1 x 8 (16 MPL) 1 x 8 (16 MPL)
MP-Bus devices via LMPBUS-804 4 x 8 (16 MPL) 4 x 8 (16 MPL) 4 x 8 (16 MPL)
MP-Bus devices (maximum) 80 80 80
Resource limits
Total number of data points
30 000
LonMark Schedulers 100
OPC data points 10 000 LonMark Alarm Servers 1
BACnet objects 2 000 (analog, binary, multi-state) E-mail templates 100
BACnet client mappings 5 000 Math objects 100
BACnet calendar objects 25 Alarm logs 10
BACnet scheduler objects 100 (64 data points per object) M-Bus data points 1 000 
BACnet notification classes 32 Modbus data points 2 000 
Trend logs (BACnet or generic)
512 (4 000 000 entries, ≈ 60 MB)
KNX TP1 data points 1 000
Total trended data points 1 000 KNXnet/IP data points 1 000
CEA-709 network variables (NVs) 2 000 Connections (Local / Global) 2 000 / 250
CEA-709 Alias NVs 2 000 Number of L-WEB clients 32 (simultaneously)
CEA-709 External NVs (polling) 1 000 L-IOB I/O Modules (via LIOB-IP) 2
CEA-709 address table entries 1 000 (non-ECS mode: 15) EnOcean data points 10 per EnOcean device
LonMark Calendar 1 (25 calendar patterns) SMI devices (per channel) 16
MP-Bus devices (per channel) 8 (16 MPL)