EU Cookie Law Script 1

     We use cookies to make our websites easier to use. By browsing our websites you agree to our use of cookies.

LIOB-BIP I/O Controller BACnet/IP

liob-580_icon.jpg
CEA-709OPC XML-DAOPC UASNMPAlarming (Alarm Management)SchedulingTrending (Historic Data Logging)E-mail NotificationEthernet (Ethernet Switch)Local I/OsLocal ConnectionGlobal ConnectionLocal Manual OperationRemote AccessVNC (Virtual Network Computing)Web Server for Device ConfigurationMathematical FunctionsIEC 61131 – L-LOGICADBackup / RestoreLIOB-IPNetwork SecurityLWEB-900 Integrated Building Management SystemLWEB-802/803 VisualizationIEC 61131 – L-STUDIOIEC 61499 – L-STUDIOUL Recognized ProductBTL-Certified Product

Index

 

LIOB-58x I/O Controllers are IP-enabled, compact, programmable automation stations for BACnet/IP networks with physical inputs and outputs and integrated graphical visualization.

BACnet/IP over Ethernet

The LIOB-58x I/O Controller is equipped with two Ethernet ports including a built-in Ethernet switch. This allows for building a daisy chained line topology of up to 20 devices, which reduces costs for network installation. Dual Ethernet port devices also allow the setup of a redundant Ethernet installation (ring topology), which increases reliability. The redundant Ethernet topology is enabled by the Rapid Spanning Tree Protocol (RSTP), which is supported by most managed switches.

Technology data points are automatically exposed as OPC tags via the integrated OPC server (OPC XML-DA). The L-IOB I/O Controllers further allow data exchange over global connections (network-wide data exchange), offer AST™ functions (Alarming, Scheduling, and Trending), store custom graphic pages for visualization in LWEB‑802/‌803, and can be seamlessly integrated in the LWEB‑900 Building Management System. LIOB-58x I/O Controllers implement the BACnet Building Controller (B-BC) profile and are BTL tested and WSPcert certified.

Local Operation and Override

All L-IOB I/O Controllers are equipped with an LCD display (128x64) with backlight and jog dial for manual local operation and override. Device and data point information is displayed in text form and via graphical symbols.

LIOB-58x

LIOB-BIP I/O Controller BACnet/IP Products


LIOB-580
LIOB-580

LIOB-BIP I/O Controller: 8 UI, 2 DI, 2 AO, 8 DO (4 x Relay 6 A, 4 x Triac 0.5 A)

Add this product to the Request for Quote
Related documents and software for LIOB-580
3D View for LIOB-580

LIOB-581
LIOB-581

LIOB-BIP I/O Controller: 8 UI, 12 DI

Add this product to the Request for Quote
Related documents and software for LIOB-581
3D View for LIOB-581

LIOB-582
LIOB-582

LIOB-BIP I/O Controller: 6 UI, 6 AO, 8 DO (8 x Relay 6 A)

Add this product to the Request for Quote
Related documents and software for LIOB-582
3D View for LIOB-582

LIOB-583
LIOB-583

LIOB-BIP I/O Controller: 6 UI, 6 AO, 5 DO (4 x Relay 16 A, 1 x Relay 6 A)

Add this product to the Request for Quote
Related documents and software for LIOB-583
3D View for LIOB-583

LIOB-584
LIOB-584

LIOB-BIP I/O Controller: 7 UI, 4 AO, 7 DO (5 x Relay 6 A, 2 x Triac 0.5 A), 1 Pressure Sensor

Add this product to the Request for Quote
Related documents and software for LIOB-584
3D View for LIOB-584

L-LOGICAD-USB
L-LOGICAD-USB

IEC 61131-3 programming tool, single license, includes USB dongle

Add this product to the Request for Quote
Related documents and software for L-LOGICAD-USB

L-STUDIO-LIOB
L-STUDIO-LIOBLicense for L‑IOB to activate the L‑STUDIO runtime (for LIOB-48x/580/581/582/583/584 V2)
Add this product to the Request for Quote
Related documents and software for L-STUDIO-LIOB

LPOW-2415A
LPOW-2415A

LIOB-Connect Power Supply, 24 VDC, 15 W

Add this product to the Request for Quote
Related documents and software for LPOW-2415A
3D View for LPOW-2415A

LPOW-2415B
LPOW-2415B

Power supply unit with power connector 24 VDC, 15 W

Add this product to the Request for Quote
Related documents and software for LPOW-2415B
3D View for LPOW-2415B

L-TEMP2
L-TEMP2

External temperature sensor (NTC10K) for use with L-IOB Universal Inputs

Add this product to the Request for Quote
Related documents and software for L-TEMP2


Features

  • Automation station with physical input and outputs
  • Programmable with L‑LOGICAD (IEC 61131‑3) or L-STUDIO* (IEC 61131‑3 or IEC 61499)

  • Dual Ethernet/IP interface
  • Manual operation using the jog dial
  • 128x64 graphic display with backlight
  • Local access to information about device status and data points in clear text and symbols
  • Stores customized graphical pages
  • Visualization of customized graphical pages through LWEB‑900 (building management), or LWEB‑802/803
  • Integrated Web server for the device configuration and for monitoring of data points
  • Extension with physical inputs and outputs using one LIOB I/ O Module (LIOB‑45x/55x)
  • Compliant with ANSI/ASHRAE–135‑2012 and ISO 16484‑5:2012 standard
  • B-BC (BACnet Building Controller) functionality, BTL certified
  • BACnet objects for integration on BACnet/IP channels
  • BACnet Client Mappings for integration on BACnet/IP channels
  • Alarming, Scheduling, and Trending (AST ™)
  • Event-driven e-mail notification
  • Math objects to execute mathematical operations on data points
  • Built-in OPC XML-DA and OPC UA server
  • Stores user-defined project documentation

*requires L-STUDIO-LIOB software license


 

Specification

Dimensions in mm [inch]

 LIOB-580

 

LIOB-580_dimensions

 

LIOB-581

 

LIOB-581_dimensions

 

LIOB-582

 

LIOB-582_dimensions

 

LIOB-583

 

LIOB-583_dimensions

 

LIOB-584

 

LIOB-584_dimensions

 

 

General Specifications
Dimensions (mm) 107 x 100 x 75 (L x W x H)
Installation DIN rail mounting following DIN 43880, top hat rail EN 50022
Operating conditions 0 °C to 50 °C, 10 – 90 % RH, noncondensing, degree of protection: IP40, IP20 (terminals)
Power supply 24 VDC / 24 VAC ±10 %
Program cycle time Down to 10 ms
L-IOB I/O Module 1 L‑IOB I/ O Module of type LIOB‑BIP
Interface 2 x Ethernet (100Base-T):
OPC XML‑DA, OPC UA
BACnet/ IP,
LIOB‑IP
Resource limits   
Total number of data points
2 000 Total trended data points  100
OPC XML‑DA data points 300  E-mail templates 20 
BACnet objects 300 (analog, binary, multi-state) Math objects 20 
BACnet client mappings 300  Alarm logs
BACnet calendar objects 25 Connections (Local / Global) 200 / 100 
BACnet scheduler objects 10 Number of L-WEB clients 8
BACnet notification classes 32 L-IOB I/O Module  1 (LIOB-BIP)
Trend logs (BACnet or generic) 50 (390 000 entries, ≈ 6 MB)    
Specifications LIOB-BIP I/O Controller (LIOB-58x)
Types LIOB-580 LIOB-581 LIOB-582 LIOB-583 LIOB-584
Power consumption 4.5 W (all Relays on) 4.5 W 4.5 W (all Relays on) 4.5 W (all Relays on) 4.5 W (all Relays on)
Universal Input (UI) 8 8 6 6 7
Digital Input (DI) 2 12 - - -
Analog Output (AO) 2 - 6 6 4
Digital Output (DO)

8 (4 x Relay 6 A, 4 x Triac 0.5 A)

-

8 (8 x Relay 6 A)

5  (4 x Relay 16 A, 1 x Relay 6 A)

7 (5 x Relay 6 A, 2 x Triac 0.5 A)

Digital output specification

Please refer to the “General Input and Output Specification of LOYTEC devices” for more details.

Differential Pressure Sensor - - - - 0-500 Pa
Runtime licenses
Type LIOB‑580/581/582/583/584 LIOB‑580/581/582/583/584 (V2)
Programming, Tools L‑LOGICAD software (IEC 61131‑3)

L‑LOGICAD software (IEC 61131‑3)
L-STUDIO software (IEC 61131‑3 or IEC 61499 )

Licence

L‑STUDIO: n/a
L‑LOGICAD: included

L‑STUDIO: upgradable
L‑LOGICAD: included

 


General Input and Output Specification of LOYTEC devices

UI Universal Input

UIs are universal inputs for four different input types. They have an input voltage range of 0 V to 10 V, and can withstand up to 30 V. The UIs correspond to class 1 with a relative accuracy of ±1 % (of measured value) between 1 V and 10 V, and an absolute accuracy of ±10 mV between 0 V and 1 V. The ADC resolution is 16 bits. Galvanically isolated sensors resp. switches must be connected. Universal inputs can be configured as:

  • Binary Input (Digital Input)

    Input impedance > 20 kΩ, sampling period 10 ms.
    • In voltage mode, the threshold values are < 0.8 V for low level and > 2 V for high level.
    • In resistance mode, the threshold values are < 1.9 kΩ for low level and > 6.7 kΩ for high level.
    Between the threshold values, the resulting level of the UI is not defined.
  • Voltage Metering 0-10 V

    Input Impedance > 20 kΩ, sampling period < 1 s.
  • Current loop 4-20 mA

    Input Impedance > 20 kΩ, sampling period < 1 s. An internal shunt of 249 Ω is available for some universal inputs. Otherwise, an external resistor of 249 Ω must be used as a shunt.
  • Resistance Measurement

    Input Impedance 10 kΩ, sampling period < 1 s. Resistors in the range of 1 kΩ to 100 kΩ can be measured. For popular temperature sensors (e.g. Pt1000, NTC10K, NTC1K8, Ni1000) fixed internal translation tables are provided. For all other temperature sensors, translation tables can be defined in the configuration tool and used on the device.

The average sampling period p of analog inputs depends on the number of active (non-disabled) universal inputs n that are configured in analog mode. The formula for p is:

p = n * 125 ms

This means if e.g. only two UIs are configured as analog inputs, a new sample is taken every 250 ms (on average) for each of the two inputs. The UIs configured as digital inputs are unaffected (sampling period always 10 ms) by this formula.

DI – Digital Input, Counter Input (S0-Pulse)

DIs are fast binary inputs, which can also be used as counter inputs (S0). They follow the S0 specification for electric meters and have a sampling rate of 10 ms. They change state at a load of 195 Ω between the DI terminal and GND. Galvanically isolated sensors resp. switches must be connected.

AO – Analog Output

AOs are analog outputs with a signal range of 0 to 10 V (up to 12 V), a resolution of 10 bits, and a maximum output current of 10 mA (20 mA @ 12 V), short circuit proof (2 outputs at a time). The accuracy over the whole range is ±100 mV.

DO – Digital Output

The following digital outputs are available:

  • Relay 6A Output: Switching capacity 6A, 250VAC resp. 30VDC. Max in-rush current 6A, max. 600W (resistive) @ 250VAC.
  • Relay 10A Output: Switching capacity 10A, 250VAC resp. 30VDC. Max in-rush current 10A, max. 1600W (resistive) @ 250VAC.
  • Relay 16A Output: Switching capacity 16A, 250VAC resp. 30VDC. Max in-rush current 80A, max. 2000W (resistive) @ 250VAC.
  • TRIAC Output: Switching capacity 0.5A, 24 to 230VAC. External relays must not be connected.

When switching higher loads than specified an interface relay must be used and a quenching circuit like a varistor or RC element must be used at the selected LOYTEC device.

PRESS – Pressure Sensor