EU Cookie Law Script 1

     We use cookies to make our websites easier to use. By browsing our websites you agree to our use of cookies.

LIOB-BIP I/O Controller BACnet/IP

liob-580

Index

 

Specification

Dimensions in mm [inch]

 LIOB-580

 

LIOB-580_dimensions

 

LIOB-581

 

LIOB-581_dimensions

 

LIOB-582

 

LIOB-582_dimensions

 

LIOB-583

 

LIOB-583_dimensions

 

LIOB-584

 

LIOB-584_dimensions

 

 

General Specifications
Dimensions (mm) 107 x 100 x 75 (L x W x H)
Installation DIN rail mounting following DIN 43880, top hat rail EN 50022
Operating conditions 0 °C to 50 °C, 10 – 90 % RH, noncondensing, degree of protection: IP40, IP20 (terminals)
Power supply 24 VDC / 24 VAC ±10 %
Program cycle time Down to 10 ms
L-IOB I/O Module 1 L‑IOB I/ O Module of type LIOB‑BIP
Interface 2 x Ethernet (100Base-T):
OPC XML‑DA, OPC UA
BACnet/ IP,
LIOB‑IP
Resource limits   
Total number of data points
2 000 Total trended data points  100
OPC XML‑DA data points 300  E-mail templates 20 
BACnet objects 300 (analog, binary, multi-state) Math objects 20 
BACnet client mappings 300  Alarm logs
BACnet calendar objects 25 Connections (Local / Global) 200 / 100 
BACnet scheduler objects 10 Number of L-WEB clients 8
BACnet notification classes 32 L-IOB I/O Module  1 (LIOB-BIP)
Trend logs (BACnet or generic) 50 (390 000 entries, ≈ 6 MB)    
Specifications LIOB-BIP I/O Controller (LIOB-58x)
Types LIOB-580 LIOB-581 LIOB-582 LIOB-583 LIOB-584
Power consumption 4.5 W (all Relays on) 4.5 W 4.5 W (all Relays on) 4.5 W (all Relays on) 4.5 W (all Relays on)
Universal Input (UI) 8 8 6 6 7
Digital Input (DI) 2 12 - - -
Analog Output (AO) 2 - 6 6 4
Digital Output (DO)

8 (4 x Relay 6 A, 4 x Triac 0.5 A)

-

8 (8 x Relay 6 A)

5  (4 x Relay 16 A, 1 x Relay 6 A)

7 (5 x Relay 6 A, 2 x Triac 0.5 A)

Digital output specification

Please refer to the “General Input and Output Specification of LOYTEC devices” for more details.

Differential Pressure Sensor - - - - 0-500 Pa
Runtime licenses
Type LIOB‑580/581/582/583/584 LIOB‑580/581/582/583/584 (V2)
Programming, Tools L‑LOGICAD software (IEC 61131‑3)

L‑LOGICAD software (IEC 61131‑3)
L-STUDIO software (IEC 61131‑3 or IEC 61499 )

Licence

L‑STUDIO: n/a
L‑LOGICAD: included

L‑STUDIO: upgradable
L‑LOGICAD: included